CVE-2012-6435

Rockwell Automation ControlLogix PLC Improper Access Control

7.8 high EPSS 42.7%

Published 24 Jan 2013 Updated 3 Jun 2026 CNA: icscert

Description

When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the CPU to stop logic execution and enter a fault state, a DoS can occur. This situation could cause loss of availability and a disruption of communication with other connected devices.

Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400

Severity (CVSS)

7.8 high CVSS 2.0 from icscert (CNA)
AV:N/AC:L/Au:N/C:N/I:N/A:C
Attack vector
network: an attacker can reach the vulnerable part over the network
Attack complexity
low
Authentication
none: the attacker does not need to log in
Impact
confidentiality none, integrity none, availability complete
7.5 high CVSS 3.1 from CISA (ADP)
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Attack vector
network: an attacker can reach the vulnerable part over the network, often from the internet
Attack complexity
low: an attack works without special conditions
Privileges required
none: the attacker does not need an account
User interaction
none: nobody has to click or open anything
Scope
unchanged: the damage stays inside the vulnerable component
Impact
confidentiality none, integrity none, availability high: what an attacker can read (confidentiality), change (integrity) or stop (availability)

Exploitation

EPSS 42.7%: the probability of exploitation activity in the next 30 days, from the EPSS model of FIRST. The score is higher than 99.0% of all scored CVEs. Scores of 27 Nov 2026.

The assessment of CISA (SSVC, 3 Jun 2026):

Exploitation
none: CISA did not find evidence of exploitation or a public proof of concept
Automatable
yes: an attacker can automate the attack across many targets
Technical impact
partial: limited control or limited data

Weakness

Affected products

As the CNA lists them.

ProductVersions
1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules
affected All
Other versions: unaffected
CompactLogix L32E and L35E controllers
affected All
Other versions: unaffected
1788-ENBT FLEXLogix adapter
affected All
Other versions: unaffected
1794-AENTR FLEX I/O EtherNet/IP adapter
affected All
Other versions: unaffected
ControlLogix, CompactLogix, GuardLogix, and SoftLogix
affected up to and including 18
Other versions: unaffected
CompactLogix and SoftLogix controllers
affected up to and including 19
Other versions: unaffected
ControlLogix and GuardLogix controllers
affected up to and including 20
Other versions: unaffected
MicroLogix
affected 1100
affected 1400
Other versions: unaffected

Is my server affected?

This CVE is in 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules of Rockwell Automation, which Linux distributions and language package managers do not ship. The advisory of the vendor is in the references below.

Vulnpocalypse matches the package lists of Linux servers and containers against the Trivy vulnerability database, which does not list this product.

References

Other references

Source: the record CVE-2012-6435 of the CVE List (CVE Program), CVE Terms of Use; the CISA KEV catalog and the CISA ADP container; EPSS of FIRST; the CWE catalog of MITRE, CWE Terms of Use. The text of the record is shown as published. Data sources and licences.